Tower Loop Products

Product Application Notes Ingrediants Calcium M Alk Dose Phosphonate Molybdate
       
Tower Treatment  
C20-C Tower Scale Control Phosphonates 500 max 200 max 10-25 2-5  
  Corrosion Control Triazole 1000 max 1000max 20-40 4-8  
  Dispersants Polymers 1200 max 400 max 50 11 ppm  
C20-C-STX Start-up/Catch Up (same as C20-C) (1 Stick = 100 ppm/1000 gal)  
   
C20M-C Tower Moly Tracer (similar to C20 (same as C-20) 10-25 1.5-3.5 .75-2.0
  w /Moly Tracer) 20-40 3-6 1.5-3.0
C20M-C-STX Start-up/Catch Up (same as C20M-C) (1 Stick = 100 ppm/1000 gal) 50 7 4
Higher Corrosive Conditions
C22-C Tower Higher Corrosion Phosphonates (same as C-20) 10-25 2-4 0.5-1.0
      Protection Triazole 20-40 3-6.5 0.8-1.6
  Moly Tracer Polymers 50 8 2.0
C22-C-STX Start-up/Catch Up (same as C22-C) (1 Stick = 100 ppm/1000 gallons)  
   
C22Z-C Tower Highest Corrosion (same as C-20) Zinc
      Protection w/Zinc 10-25 1-2.5 0.4-1.0
  Scale Control Phosphonates 20-40 2-4 0.8-1.6
  Corrosion Control Triazole 50 5 2.0
    Dispersants Polymers          
Dispersants
CPEN-C Tower Dispersants Bio-dispersant (normal: 60-120ppm, 3 x/wk) ATP or Colony Count
  Penetrants General- dispersant (Heavily fouled: 100-200ppm daily)  
  (Moderately fouled: 100-200ppm 3 x/wk)  
CPEN-8000 Tower Dispersants Bio-dispersant (normal: 80-150ppm, 3x/wk) ATP or Colony Count
  Penetrants General- dispersant (Heavily fouled: 200ppm daily)  
        (Moderately fouled: 200ppm 3 x/wk)    
Biocides
C-100G - Bio-Brom Tower DBNPA EPA Reg. Biocide (1lb/100,000 system gallons, 2-3 x/wk)   ATP or Colony Count
C-200 - Bio Bag Tower Broad Spectrum EPA Reg. Biocide (1 bag/2000 system gallons, 1-2 x/wk)    ATP or Colony Count
Closed Loops
L1-C Closed Loop Corrosion Control Borax/Nitrite 1 lb./150 gallons system water Nitrite  
L1-C-STX Start-up/Catch Up (same as L1-C) (1 stick/100 gallons system water) 500ppm  
(No Nitrite)  
L2-C Closed Loop Corrosion Control 1 lb./500 gallons system water 8-10
L2-C-STX Start-up/Catch Up (sames as L2-C) (1 stick/400 gallons system water)  
(No Nitrite/Molybdate)  
L3-C Closed Loop Corrosion Control Borax/Silicates 1 lb /500 gallons system water 15-20  
L3-C-STX Start-up/Catch Up (same as L3-C) (1 stick/500 gallons system water)    
Specialty Products
CWR-C Tower "White Rust Prevent" Phosphate 300 max 300 max 250ppm 100ppm PO4  
  Polymer pH 6.5-8.0  
  Dispersant  
  Triazole  
CWR-C-STX Start-up/Catch Up (same as CWR-C) (1 stick/500 gallons system water) (Same)  
   
CACD-C pH Adjustment Descaler Sulfamic acid (consult for specific cleaning recommendations)  