CPEN-C Cooling Water Treatment
Solid-Concentrate
Download in MS Word Format
Description
Solid-Concentrate CPEN-8000 is a cooling system dispersant and penetrant which assists in the prevention and removal of organic materials & foulants. This product was designed to supplement cooling system inhibitor/dispersants & biocides to maintain clean surfaces in heat transfer equipment and cooling towers. CPEN-8000 penetrates the matrix of organic deposits which then sloughs off and disperses. It also functions as a general corrosion inhibitor & cleaner for heavily fouled systems. Use should be in conjuction with biocides to assist in maintaining a clean system.
 
Application/Feedrate
CPEN-8000 should be fed at a rate of 80-150 ppm to maintain already clean surfaces, 1-3 times per week. For systems that have a greater tendency to foul, feed at a rate of 200 ppm, 2-3 times per week. To clean heavily fouled systems, feed at a rate of 200 ppm daily, until clean. Always feed a biocide to kill bacteria & algae in the system. Care should be taken, when cleaning, to prevent clogging of screens and strainers in heavily fouled systems when applying this product. NOTE: This product may cause foaming when fed at high levels.
 
Testing & Control
ATP or colony count
 
Feeding
Feed product from a Solv-all™100 or similar system/board.
 
Packaging/Storage/Handling
Packaged in 4 x 1 gallon containers per case. Case weighs 36 lbs. Follow MSDS Properly stored product will remain effective 24 - 36 months. Store in cool, dry area
 
The above information is based on data available to us and is believed to be correct. As the conditions or methods of use are beyond our control, we do not assume any responsibility and expressly disclaim any liability for any use of this material and this information is furnished upon the condition that the person receiving it shall make his own determination for the suitability of the material for his particular purpose. the information contained herein is believed to be true and accurate but all statements or suggestions are made without warranty, expressed or implied, regarding the accuracy of this information, the hazards connected with the use of the material, the results to be obtained from the use thereof, or any such use will not infringe any patent. Compliance with federal, state, and local laws and regulations remain the responsibility of the user.
 
United Supply Service, Inc.
Questions or comments? Email Webmaster