C22-C-STX Cooling Water Treatment Solid-Concentrate
Start-up/Catch-up Stick
Download in MS Word Format
Description
Packaged in a water soluble bag,designed to treat open cooling tower water systems when first started up in order to obtain an adequate amount of inhibitor at system start-up. Also a good catch up solution to systems that have lost water or where the inhibitor feed has been absent for a period. For small systems where metering inhibitor into the system is not practical. Solid-Concentrate C22-C-STX is a proprietary water treatment for CORROSIVE conditions that utilizes the very latest anti-scaling, anti-fouling, & corrosion inhibition technology. C-22-C-STX approach to inhibit ferrous metal corrosion utilizes both cathodic & anodic protection, copper inhibitors, & molybdate. Contains PBTC phosphonate, HEDP phosphonate, polymaleic acid, Ter-polymer, HPA, POCA, triazole, molybdate.
 
Application/Feedrate
C22-C-STX starting federate is 50 ppm. More or less may be needed, based on corrosive index of particular water

  FEED RATE PHOSPHONATE MOLYBDATE (as Mo)
  10 - 25 PPM 2 - 4 PPM 0.5 - 1.0 ppm
  20 - 40 PPM 3 - 6.5 PPM 0.8 - 1.6 ppm
  50 PPM 8 PPM 2 ppm
* each bag & contents, when added to 1,000 gallons of system volume will yield 100ppm of product..
 
Testing & Control
Hach, Taylor & other organophosphonate/moybdate test kits. (see your service rep for details)
 
Feeding
When dosed into system, attempt to find a high flow area in the sump of the cooling tower or inside make-up tank that is accessible. Dissolving rates will vary depending upon water composition, temperature, and flow rate
 
Packaging/Storage/Handling
Packaged in 30 x 0.8 lb water-soluble bags (each enclosed in a corrugated container) per case. Case weighs 24 lbs. Follow MSDS. Properly stored product will remain effective 24 - 36 months. Store in cool, dry area.
 
The above information is based on data available to us and is believed to be correct. As the conditions or methods of use are beyond our control, we do not assume any responsibility and expressly disclaim any liability for any use of this material and this information is furnished upon the condition that the person receiving it shall make his own determination for the suitability of the material for his particular purpose. the information contained herein is believed to be true and accurate but all statements or suggestions are made without warranty, expressed or implied, regarding the accuracy of this information, the hazards connected with the use of the material, the results to be obtained from the use thereof, or any such use will not infringe any patent. Compliance with federal, state, and local laws and regulations remain the responsibility of the user.
 
United Supply Service, Inc.
Questions or comments? Email Webmaster