C20-C-STX Cooling Water Treatment Solid-Concentrate
Start-up/Catch-up Sticks
Download in MS Word Format
Description
Packaged in a water soluble bag,designed to treat open cooling tower water systems when first started up in order to obtain an adequate amount of inhibitor at system start-up. Also a good catch up solution to systems that have lost water or where the inhibitor feed has been absent for a period. For small systems where metering inhibitor into the system is not practical. Solid-Concentrate C20-C-STX is a proprietary water treatment for conditions that utilizes the very latest anti-scaling, anti-fouling, & corrosion inhibition technology. Scale, dispersing & corrosion inhibitors working with conventional chemistry provide protection at low product feed rates (refer to laboratory scaling study). Contains PBTC phosphonate, HEDP phosphonate, polymaleic acid, Ter-polymer, HPA, triazole
 
Application/Feedrate
C20-C-STX can be used in tower water systems that contain up to 1200 PPM calcium /400 PPM alkalinity and /or 1000 PPM calcium/1000ppm alkalinity utilizing the below-listed feed rates (supported by the Buckman Lab Study dated 9/5/00)

WATER QUALITY FEED RATE PHOSPHONATE
500 PPM calcium, 200 PPM alkalinity 10 - 25 PPM 2 - 5 PPM
1000 PPM calcium, 1000 PPM alkalinity 20 - 40 PPM 4 - 8 PPM
1200 PPM calcium, 400 PPM alkalinity 50 PPM 11 PPM
* each bag & contents, when added to 1,000 gallons of system volume will yield 100ppm of product
 
Testing & Control
Hach, Taylor & other organophosphonate test kits. (see your service rep for details)
 
Feeding
When dosed into system, attempt to find a high flow area in the sump of the cooling tower or inside make-up tank that is accessible. Dissolving rates will vary depending upon water composition, temperature, and flow rate.
 
Packaging/Storage/Handling
Packaged in 30 x 0.8 lb water-soluble bags (each enclosed in a corrugated container) per case. Case weighs 24 lbs. Follow MSDS. Properly stored product will remain effective 24 - 36 months. Store in cool, dry area.
 
The above information is based on data available to us and is believed to be correct. As the conditions or methods of use are beyond our control, we do not assume any responsibility and expressly disclaim any liability for any use of this material and this information is furnished upon the condition that the person receiving it shall make his own determination for the suitability of the material for his particular purpose. the information contained herein is believed to be true and accurate but all statements or suggestions are made without warranty, expressed or implied, regarding the accuracy of this information, the hazards connected with the use of the material, the results to be obtained from the use thereof, or any such use will not infringe any patent. Compliance with federal, state, and local laws and regulations remain the responsibility of the user.
 