L1-C
Closed Loop Water Treatment
Solid-Concentrate
|
| Download
in MS Word Format |
Description
Solid form, complete system corrosion inhibition treatment for
chill water & hot water boilers. Contains nitrite, borax,
acrylates, phosphino corrosion inhibitors, and copper metal
inhibitors |
| |
Function
L1-C is a proprietary product to be used as a stand-alone treatment
for corrosion inhibition in closed water systems |
| |
Application/Feedrate
Feedrate: 1 lb per 150 gallons of water capacity. |
| |
Testing & Control
Nitrite: 500 ppm |
| |
Feeding
Feed product from a Product Dissolution Board or similar system/board. |
| |
Packaging/Storage/Handling
Packaged in 4 x 1 gallon containers per case. Case weighs 48
lbs. Follow MSDS. Properly stored product will remain effective
24 - 36 months. Store in cool, dry area. |
| |
| The above information is based
on data available to us and is believed to be correct. As the
conditions or methods of use are beyond our control, we do not
assume any responsibility and expressly disclaim any liability
for any use of this material and this information is furnished
upon the condition that the person receiving it shall make his
own determination for the suitability of the material for his
particular purpose. the information contained herein is believed
to be true and accurate but all statements or suggestions are
made without warranty, expressed or implied, regarding the accuracy
of this information, the hazards connected with the use of the
material, the results to be obtained from the use thereof, or
any such use will not infringe any patent. Compliance with federal,
state, and local laws and regulations remain the responsibility
of the user. |